Product Specifications
Technical Performance Specifications
All Phasemaster® Rotary Phase Converters are built to meet the following electrical specifications:
Voltage Input |
208V, 230V, 460V field changeable on most non-automatic types |
Voltage Output |
Equals 3-phase equivalent of 1-phase input voltage |
Ratings |
1-100 HP single units, may be paralleled up to 500HP |
% Regulation |
2-5% at full load output |
Harmonic Content |
<1% |
Power Factor |
95 or greater at full load |
Operating Efficiency |
>95% at full load |
Operating Reliability |
MTBF 50,000 hours |
Following is a detailed engineering design specification for all rotary converters.
I. GENERAL
Phase Converters for changing single-phase input to three-phase output shall be rotary type. Static converters using autotransformers and/or capacitors only shall not be used. Phase converter shall be capable of starting and running single or multiple motor loads at full rated capacity. The converter shall be capable of operating motor and resistance loads simultaneously.
II. CONSTRUCTION
The rotary phase converter shall be single piece construction and capable of starting the load without external or separate capacitor panels. The rotary frame portion of the converter shall be cast iron or rolled steel drip proof construction. If required by operating environment, converters shall be totally enclosed with all control components mounted in a NEMA 3R enclosure. Rotary converters shall be built on a NEMA frame at least two sizes larger than the frame size of the load. Manufacturer shall identify the frame size of the converter proposed.
Rotary converters shall operate at not more than 1800 RPM. The converter shall have a high resistance rotor without cast fins. All converter capacitors shall be sealed oil type with integral circuit interrupters. Electrolytic type or PCB filled capacitors are not acceptable. Individual capacitors shall be rated to withstand not less than 370 volts continuously on 240V converters, and 600V on 480V units. The capacitor compartment shall be mounted on top of the rotary base. Capacitor boxes mounted on the side of the rotary base are not acceptable except on converters of totally enclosed construction.
III. CONTROLS
Depending on the control requirements of the load to operated, rotary converters shall be designated as non-automatic, switched, or automatic. If not specified herein, bidder shall expressly identify which control type is being offered for each converter proposed.
Non-Automatic converters shall be supplied with a motor style conduit/connection box. Connection leads shall be clearly marked and supplied with crimped ring terminals. External switch and fuses will be supplied by others based on manufacturer’s size recommendation. Switched converters shall contain built-in disconnect switch and time delay fuses located in a side-mounted enclosure on the converter. Switched converters shall be equipped with input and output terminal blocks to accommodate the recommended input and output feeders. The switch shall provide on-off converter control and shall isolate all three output lines in off position.
Automatic converters for unattended load operation shall be equipped with magnetic controls to start converter on demand from a load controller. Controls shall be located in a side-mounted compartment and shall at a minimum include primary fuses, contactor, timing relay and terminal blocks sized for input and output feeders. Converter control scheme shall enable it to start from at least two separate external pilot devices. The controller shall lock out the load until the converter has reached full operating speed. Manufacturer shall submit a control diagram to show how this will be accomplished.
IV. ELECTRICAL RATINGS
The converter shall be rated to operate on 208, 230 or 460 volts at 60 hertz or, 220 or 380/415 volts at 50 hertz. Non-automatic converters to 50 HP shall be field changeable to operate at 230 or 460 volts. It shall be capable of supplying a balanced three-phase output voltage and current into a total induction motor load equal to three times the nameplate rating of the largest motor to be started. All converters shall be capable of starting on half voltage without damage to windings or other components and shall be capable of operating continuously under no-load without overheating.
V. SOUND LEVELS
The maximum overall noise level output from the phase converter shall not exceed ** DBA as measured at a distance of one meter from the converter surface according to procedures defined by Industry Standard IEEE-85 Test Procedure for Airborne Sound Measurements on Rotating Electric Machinery.
** Refer to factory for maximum sound level specification for the converter model specified
VI. TESTING
Each converter supplied under this specification shall have been tested at the manufacturer’s site to verify compliance with specification based on CSA Std. C22.2 and UL Std. 508.
Additional production tests shall include:
- Measurement of output voltage at no-load
- Measurement of output voltage at full load
- Measurement of no-load input current
- One minute high potential test at 2.5 KV
- Half voltage acceleration time test
- Noise level test
Purchaser shall have the right to witness all tests prior to shipping provided manufacturer is given sufficient advance notice.
Prior to shipment: Manufacturer shall submit copy of test data showing model numbers of the units being supplied upon request
At time of shipment: Manufacturer shall submit production test reports on each converter shipped.
VII. FIELD SERVICE
If requested, Manufacturer shall provide at buyer’s expense, a field service engineer to assist in start-up or resolution of operating problems. Manufacturer shall also provide a contact number for technical support outside of regular business hours.
VIII. ACCEPTABLE CONVERTER
Converter shall be Phasemaster type as manufactured by Kay Industries, Inc. of South Bend, IN, USA.
VIIII. TECHNICAL DATA REQUIRED
Bidder to submit with proposal:
- Converter model number
- Nameplate starting HP rating, maximum total running HP
- Rotary converter frame size and RPM
- Weight and dimensions
- Starting current and no-load idle current
- Recommended single and three-phase feeder sizes
- Control voltage (Automatic converters)
- Fuse rating (Automatic and switched converters)
- Guaranteed maximum output amps on manufactured leg at 230 Volts
- Photograph of converter proposed
- Connection diagrams